If both axes throw servo error when you try to jog the issue must be common to both axes:
- Do the green lights on the servo amps light up when you turn the serovos on?
- If not lit, check the voltage between the two outboard wires on the green connectors on the amps: this should be about 70VDC.
- If they are lit, check the voltage on the two inboard wires on the green connectors on the amps: if they measure about 70VDC, then the armature circuit in both motors is open.
- Verify that light on the armature relay is lit.
- If not lit, verify that J9 on connect card is connected. On earliest G3's, wires to the armature relay were soldered to diode D1 near relay 1CR; check these connections.
- If it is lit, scroll down to troubleshoot armature relay circuit.
- If the the green leds on the amps are not lit, but voltage between the two outboard wires on the green connectors is about 70VDC, the amps may not be enabled:
- Check the voltage between pin 11 and pin 5 on the small connector on the amps. It should read about 0VDC.
(Pin 11 is yellow on X amp, white on Z amp. You will need tiny meter probes, or a paperclip, to access the wires on the small connector).
- If it's not about 0VDC, relay 1CR may have bad contacts. Swap 1CR with the coolant relay, or replace it if you have new one.
If only one axis throws a servo error when you try to jog:
First check the thermal overloads
On the earliest G3 CNC's, shipped before 2007, these are accessible through a finger-hole on the side of the blue cover; after about mid 2007, these are on the back panel.
When you press the tripped overload you should feel a distinct click as it resets. If it feels soft, or doesn't fully engage, the thermal overload may be bad.
If one axis doesn’t move, but it throws a servo-error in Jog-2 or Jog-3 (in Jog-1 you can see the position counter changing), the motor might be bad, or the motor armature circuit might be open.
To quickly determine if the motor is bad
(For this example, assume the Z-axis is bad)
- Set servos off, disconnect both motor cables at back of control, and connect the bad axis motor cable (Z in this example) to the good axis (X in this example).
- Jog the good axis (X in this example)
- If you still get servo error, replace the motor.
- If the bad axis (Z) moves, the motor is good and the issue is in the control.
To troubleshoot the armature relay circuit and thermal overloads
If the armature circuit is 'open', the motor terminals on the servo amp will be about the same as the bus voltage. Set servos off, reconnect motors and set servos on. Measure DC volts at motor terminals on the bad axis: if it is 60 to 70VDC, the armature circuit is open.
Examine the illustrations below:
NOTE: Before about 2007, chassis-mount thermal overloads were used; after 2007, the overloads were mounted on back panel. Refer to the appropriate illustration.:
- Tug on the red and black wires that go through the connect card; they should not pull out. (Check both axes to compare)
- With servos on, measure DC volts across the thermal overload; it should be near zero volts; if not, replace the overload. (Check both axes to compare)
- Measure between the armature relay contacts and overload terminals as shown in images below; voltage should be near zero volts; if not, replace the relay. (Check both axes to compare)